1. What is a Linear Heat Sensing (LHS) Cable?

A Linear Heat Sensing Cable is a digital heat detection system that detects fire by monitoring temperature continuously along its entire length. When a preset temperature is reached, the cable triggers an alarm, making it ideal for early fire detection in high-risk and harsh environments.


2. How does Linear Heat Sensing Cable work?

LHS cable consists of two twisted, polymer-insulated conductors. When the surrounding temperature reaches the rated alarm temperature, the insulation melts at that point, allowing the conductors to short circuit and signal a fire condition to the fire alarm panel or monitoring module.


3. What are the key applications of LHS Cable?

Linear Heat Sensing Cables are widely used in:

  • Cable trays & tunnels
  • Conveyor belts
  • Power plants & substations
  • Battery rooms
  • Warehouses & cold storage
  • Solar power plants
  • Parking garages
  • Oil & gas facilities
  • Escalators & elevator shafts

4. Why should I use Linear Heat Sensing Cable instead of smoke detectors?

Linear Heat Sensing Cable is preferred where smoke detectors are unreliable due to:

  • Dust, moisture, steam, or fumes
  • High ambient temperatures
  • Outdoor or semi-outdoor installations

LHS cables offer point-specific detection, minimal false alarms, and require very low maintenance.


5. What temperature ratings are available in LHS Cables?

LHS cables are available in multiple alarm temperature ratings, typically ranging from:

  • 70°C (datasheet)
  • 90°C (datasheet)
  • 105°C (datasheet)
  • 178°C (datasheet)

The correct rating depends on ambient temperature and application risk.


6. Is Linear Heat Sensing Cable reusable after activation?

No. LHS Cable is a digital (non-resettable) detection system. Once activated at a fire point, the affected cable section must be identified and replaced, ensuring precise fault location and system reliability.


7. Can LHS Cable be integrated with a conventional or addressable fire alarm system?

Yes. Linear Heat Sensing Cable can be integrated with:

  • Conventional fire alarm panels
  • Addressable fire alarm systems
  • Fire alarm control modules
  • Dedicated LHS interface modules

Fire Knock provides complete integration support for the Linear Heat Detection System.


8. What standards and approvals does LHS Cable comply with?

Linear Heat Sensing Cables are manufactured in compliance with international fire detection standards, making them suitable for use in industrial, commercial, and infrastructure projects. The cable is approved under the UL Standards (UL certificate)


9. How is LHS Cable installed?

Installation is simple and flexible:

  • Mounted using clips, ties, or trays
  • Can follow cable routes, conveyor belts, or equipment
  • No complex calibration required

Proper spacing and routing are designed as per site conditions and fire risk analysis.


10. What is the maximum length of a Linear Heat Sensing Cable zone?

The maximum length depends on:

  • Cable model
  • Interface module used
  • Fire alarm panel compatibility

Fire Knock assists in system design and zoning calculations to ensure compliance and performance (CONTACT: RAHUL ASHER - +91-9867064498)


11. Is Linear Heat Sensing Cable (LHS Cable) suitable for outdoor use?

Yes. Linear Heat Sensing Cable (LHS Cable) is designed to withstand:

  • High humidity
  • Dust and corrosive environments
  • Wide temperature variations

It is suitable for both indoor and outdoor installations.


12. What maintenance does Linear Heat Sensing Cable require?

LHS Cable requires minimal maintenance, typically:

  • Periodic visual inspection
  • Continuity testing during scheduled fire audits

There are no moving parts, making it highly reliable.


13. How do I select the correct LHS cable for my application?

Selection depends on:

  • Ambient temperature
  • Risk category
  • Installation environment
  • Fire alarm system type

Fire Knock provides application-specific technical guidance to ensure correct selection.


14. Are you an authorized distributor of Linear Heat Sensing Cable in India?

Yes. Fire Knock is an authorized distributor of PATOL Limited Products like Linear Heat Sensing Cable, Infrared Detector, etc in India, offering:

  • Genuine products
  • Technical support
  • System design assistance
  • Timely delivery

15. How can I get a quote or technical datasheet?

You can:

  • Contact Fire Knock through the website or contact Mr. Rahul Asher - +91-9867064498
  • Request a datasheet
  • Share your application details for a customized solution

Our technical team will assist you end-to-end.

16. Is LHS cable and LHDC cable the same?

Yes. LHS (Linear Heat Sensing) cable and LHDC (Linear Heat Detection Cable) refer to the same type of fire detection technology.

The difference is only in terminology:

·         LHS cable emphasizes the sensing function

·         LHDC cable emphasizes the detection function

Both terms describe a digital linear heat detection system that activates when the preset temperature is reached at any point along the cable. In industry usage, LHS cable, LHDC cable, and Linear Heat Detection Cable are used interchangeably.

 